Control valve common failure analysis and solutions

Column:Technical article Time:2021-03-26
The control valve is widely used in oil refining and chemical industry. It is used to control the flow rate, pressure and liquid level of the fluid in the production process...

The control valve is widely used in oil refining and chemical industry. It is used to control the flow rate, pressure and liquid level of the fluid in the production process.In the application of control valves, calculation and selection is the premise, installation and debugging is the key, use and maintenance is the purpose.If the selection of the control valve is not appropriate, improper installation or debugging is not good, it will not play a regulating role.Therefore, it is very important to be familiar with the control valve working principle and maintenance skills.

Principle of control valve

Pneumatic control valve to compressed air as power source, through the cylinder, film as the actuator, and with the help of electrical valve positioner, converter, solenoid valve, position valve and other accessories, to achieve switching or continuous adjustment, receiving DCS control signals to adjust the medium flow, pressure, temperature and other process parameters.Pneumatic valve is mainly divided into two types of gas open type and gas closed type, characterized by simple control, quick response, essential safety, no need to use explosion-proof measures.

Control valve failure mode and cause

The main failure forms of pneumatic control valve are: the internal leakage valve does not act, the opening degree fluctuates greatly, the jam phenomenon appears, the operation is normal but the flow rate does not change.The main reasons are: valve body fault, cylinder fault, locator fault, DCS fault, control cable fault, maintenance is not in place, valve quality problems, selection or design reasons, pneumatic components fault.

01. Valve body failure and countermeasures

Common faults

    1) The metal valve seat of the butterfly valve is damaged and the valve body is stuck;The butterfly valve fixing bolt falls off or the connecting bolt between the spool and the stem of the half ball valve slides. The main performance is that the spool appears to have acted but the spool does not act

    2) Internal wear of the ball valve body causes the valve to be easily stuck or the valve to act slowly;Damaged ball valve soft seal gasket causes valve to leak or get stuck.

    3) The damage of the shaft sleeve of the half ball valve causes the valve to operate difficult.

    4) steam leakage caused by high temperature aging of steam valve stem seal;The steam valve muffler falls off, causing the valve to often get stuck and the pipe to be unusually noisy.

    5) Internal leakage caused by wear or corrosion of valve stem;Damaged seal at stem packing resulting in leakage.

The reason countermeasures

    1) the cause of the spool valve seat leakage is the surface wear or corrosion of the spool valve seat, the actuator force is too small, and the valve seat thread is worn and loosened.Troubleshooting: improve the grinding joint surface, adjust the actuator and stem connection, tighten bolts or replace the spool seat.

    2) The cause of leakage between the seat ring and the valve body is that the tightening torque is too small, the surface finish of the valve body is poor, the gasket is not suitable, and the valve body has small holes or burrs.Fault treatment: increase the twisting force, clean and treat the valve body again, replace the appropriate gasket, and weld the valve body again.

    3) the cause of packing leakage is that the stem finish is not good or bending, the packing cover is not pressed or the packing type is unreasonable, the packing layer is piled too high, the packing appears corrosion pit or the packing cover deformation and damage.Fault treatment: polish valve stem and press straight, tighten or replace packing;Install spacer ring, reduce height, replace with good performance packing, repair and replace gland and associated flange bolts, etc.

    4) The valve stem and the valve vibration cause the valve stem connection to break off or break, the reason is that the torque is too large, the pin connection is not appropriate.Fault treatment mode: use the valve core stem integral part or welded valve core to connect the connector firmly and eliminate the vibration factor.The cause of valve vibration is the leakage of sealing filler, the bypass is not adjusted well, the positioner gain is too high, and the vibration source is not well supported.Fault treatment: lubricate the packing and adjust, readjust the bypass, select the low-gain positioner, and fix the valve firmly to avoid the vibration source.

02. Causes and countermeasures of cylinder failure

Common faults

    1) The actuator limit bolt falls off, resulting in air leakage of the cylinder, which causes the valve to be unable to act or to act slowly, and can not reach the predetermined opening.

    2) The damage to the O-ring of the cylinder leads to air leakage, which makes the valve difficult to operate or unable to operate.

    3) the deformation of the cylinder piston leads to the increase of friction, and the loosening of the cylinder bolt causes the cylinder to leak, thus causing the valve to operate difficult.

    4) The linkage mechanism of the cylinder driving the valve body action is loose or rusted, resulting in difficult valve action.

    5) Small cylinder capacity or cylinder spring failure leads to difficult valve action.

The reason countermeasures

    1) The cause of the leakage at the piston seal is the poor smoothness of the cylinder;The sealing of piston ring assembly is not enough, the temperature of the sealing ring is too high, and the sealing parts are damaged for too long.Fault treatment: grind the cylinder and readjust the cylinder limit bolt, select the sealing ring again according to the use temperature, and install it correctly when replacing.

    2) The treatment of cylinder limit bolt loosening: tighten the bolt again.

    3) the treatment of large piston friction: re-lubricating oil, re-cleaning and grinding cylinder and piston.

    4) the valve action is difficult to reach the fixed stroke, the actuator spring value is not enough or the spring is damaged, the position of the limit block is not accurate.Treatment: calibrate, reschedule and replace the spring.

03. Locator Fault Causes and Countermeasures

Common faults

    1) The fault of the locator circuit board causes the abnormal action of the valve.

    2) The damage or wear of the small slide valve causes the abnormal action of the valve. The reason is that the air cleanliness of the instrument is not high, or dirt enters the positioner and causes the wear of the small slide valve, which causes the abnormal action of the valve.

    3) The damage of the proportional valve of the positioner causes abnormal valve action.

    4) The damage of sliding rheostat leads to inaccurate positioning of the valve and abnormal operation of the valve. The main reason is that the ambient temperature is too high and water and other liquids enter, which leads to the damage of the rheostat.

    5) The O-sealing ring of the air source interface of the positioner is broken, which causes the broken O-sealing ring to jam the stem of the small slide valve and make it unable to act.

    6) The sealing of the gran head of the locator is not good, which leads to the water damage of the locator circuit board.

    7) due to the pipeline vibration is too large, the surrounding environment temperature is too high, humidity is too large, cause the circuit board failure.

The reason countermeasures

    1) The seal problem at the glen head leads to the water inlet of the locator and causes the circuit board damage.Fault treatment: improve the sealing of the gran head, so as to avoid the damage of the circuit board caused by the water inside the locator.

    2) due to the instrument air humidity and more dust, leading to the small slide valve into the dirt caused by the small slide valve wear, so that the valve action is not normal.Trouble handling: add air filter to improve air quality of instrument.

    3) Frequent damage of sliding rheostat and circuit board is caused by excessive ambient temperature, humidity and vibration.Fault treatment: the circuit board and the small slide valve and slide rheostat separation, made of separated valve positioner.

    4) The O-ring of the positioner often breaks, leading to the stem of the small slide valve being stuck. The main reason is that the air source pressure is too large. Normally, it should be about 0.5Mpa, and higher than 0.5Mpa will lead to faster aging of the sealing ring and easy damage.Fault treatment: keep the air source pressure at about 0.4Mpa, and provide better quality sealing ring.

04. Failures caused by process and design and countermeasures

Common faults

    1) The valve cannot be operated due to the large pressure difference in pipeline caused by the change of process parameters.

    2) Scaling of the valve body caused by the medium causes abnormal valve action.

    3) The valve cannot operate normally due to pipeline blockage.

    4) Due to the design and selection reasons, the actuator is small, the torque is not enough, the valve can not operate normally, and the material of the valve body is not appropriate, leading to the damage of the valve body.

The reason countermeasures

    1) Excessive pressure difference causes the control valve to fail to open normally.Treatment: a bypass valve is installed before and after the control valve.

    2) The control valve can not be opened normally due to scaling of the valve body due to process reasons.Treatment: increase the flushing water pipe, in addition to regularly open the valve to clean the valve body, if necessary, grinding the valve core.

    3) The control valve can not operate due to pipeline blockage.Treatment method: optimize the operation method, as far as possible not to clog the pipeline, in addition to open the pipeline flushing valve.

    4) About the design selection.Treatment method: in the design stage, try to optimize a variety of process parameters, to ensure that selection will not cause problems due to inaccurate process parameters.

05. The fault caused by DCS and countermeasures

Common faults

    1) I/O card damage without signal output, resulting in the control valve can not operate.

    2) DCS output signal is unstable, resulting in the control valve opening fluctuation, so that the control valve action is not normal.

    3) the control cable is damaged or the insulation is not good, the wiring is loose and the signal is not normal, which causes the control valve to act abnormal.

    4) Because of the maintenance is not in place, the locator water, cylinder corrosion and air leakage, air source pipe sleeve fall off and air leakage and other reasons cause abnormal action of the control valve.

    5) Because the inspection is not careful, the hidden danger is not found in time, which leads to further expansion, and finally causes abnormal action of the control valve.

The reason countermeasures

    Daily maintenance and inspection should be done well, and hidden dangers should be dealt with in time.When the opening of the control valve fluctuates, timely check whether the PID parameters are set correctly and adjust the parameters in time.

06. Failure caused by damage of pneumatic components and countermeasures

Common faults

    1) The air supply pressure is low due to the aging and damage of the air supply hose or the leakage of the stainless steel air supply pipe, which makes the operation of the control valve abnormal.

    2) Abnormal action of control valve caused by air filter fracture or dirty filter element.

    3) Abnormal action of control valve caused by low air source pressure or closed air source.

The reason countermeasures

    1) replace the air source hose or air filter with better quality;If the air source hose or air filter is found to be damaged or leak during regular inspection, or the filter element is too dirty, it is necessary to find the opportunity to replace it as soon as possible.

    2) Adjust the air source pressure to meet the minimum air source pressure requirements of pneumatic valves.

主站蜘蛛池模板: 99久久99久久久精品色圆_欧美精品国产_国产午夜亚洲精品理论片色戒_日日日噜噜噜_玖玖视频国产_国产精品高潮呻吟久久aⅴ码_成人宗合_日韩成人av网 | 成年人免费在线看网站_久久久一本精品99久久精品_av―极品视觉盛宴正在播放_国产一级18片视频_欧洲美熟女乱又伦AV_日本天堂免费_AV天堂永久资源网_亚洲视频你懂的 | free性av麻豆_亚洲一级黄色片子_欧美国产精品久久久_日本亚洲9999aⅴ_四虎影院在线视频_国产精品123区_国产一区二区三区免费观看潘金莲_久久精品国产99国产精品澳门 | 国产乱码精品一区二区三区四川人_91?网在线?看_久久综合AV免费观看_亚洲欧洲在线播放_www.嫩草视频_aa国产视频_国产日产欧美一区_h黄动漫网站 | 国产交换精品一区二区三区_中文字幕日本一区_91精品国产综合久久久久久首页_国产美女网站_久久一区免费_日本在线播放一区二区_欧美精品黄色片_www.啪啪.com | 手机看片国产福利_免费人成激情视频在线观看_FREEEⅩXX性欧美HD浪妇_谍战剧《惊弦》免费观看高清_99爱免费观看_多人运动罗志祥网站免费_免费一本色道久久一区_秋霞无码久久久精品 | 亚洲人体av_国产成人AV综合色_国产精品人_成人高潮片免费视频_久色视频在线_亚洲国产精品激情在线观看_欧美精品成人在线_中文字幕一区二区三区中文字幕 | 少妇无内裤下蹲露大唇_色999久久久精品人人澡69_91激情视频在线播放_精品国产一区在线_麻豆传媒官网_久久综合视频网_国产1区2区视频_夜夜春亚洲嫩草一区二区 | 97超碰影视_亚洲国产另类精品_欧美牲交a欧美牲交一级aa_四虎必出精品_欧美人与禽交无码免费视频_国产真人真事毛片视频_三级视频网_欧美日韩一区二 | 玩弄放荡人妻少妇系列_国产播放啪视频免费视频_精品视频一区二区在线_一区二区三区在线免费_久久99精品久久久久久蜜芽_男人操女人免费视频网站_亚洲第一偷拍视频_伊人中文 | 国产精品久久观看_亚洲性区_濑亚美莉av番号大全_国产涩涩在线观看_北条麻妃在线播放_欧美性福_黄色av网站在线_日韩猛片 | 国产精品久久久久久亚洲色_免费91_台湾佬成人_日韩精品一区在线播放_亚洲AV无码乱码在线观看代蜜桃_国产精品亚洲аv久久_国产精品久久久久四虎_亚洲AV无码乱码在线观看性色 | 狠狠色综合色区_麻豆影视在线播放_亚洲kkk444kkk在线观看_第一色网站_国产高清在线观看AV片麻豆_日韩69_影音先锋日日狠狠久久_日本熟妇XXX50 无码超乳爆乳中文字幕久久_国产精品高潮久久久久_亚洲国语_91快射_欧美在线成人午夜网站_亚洲精品NV久久久久久久久久_欧美操操操_九九久久成人 | 国产在线观看a视频_96国产精品_亚洲国产网站_KTV少少爷互囗交Gaygv_亚洲精品久久久无码白峰美_日本韩国国产_av中文在线资源_亚洲AV无码日韩AV无码导航 | 狠狠热精品免费视频_国产成人aaaaa级毛片_98版还珠格格免费观看_精品国产品国语在线不卡_最近中文字幕一区_午夜激情免费视频_人人爱人人澡_亚洲综合色在线 | 欧美一区二区片_午夜视频二区_中文天堂在线免费网站_日韩精品视频免费在线观看_日本欧美一区二区三区乱码_伊人午夜_日韩欧美成人一区二区三区_在线观看中文字幕一区二区 | 国产99九九久久无码熟妇_最新国产精品综合在线啪_极品夜夜嗨久久精品17c_精品国产第一国产综合精品_台湾佬中文娱乐网97爱爱_欧美性黑人极品hd另类_嫩草研究院在线观看_天堂在线www天堂在线 | 成年人黄色录像_日韩有码一区二区三区_中文字幕欧美日韩一区二区三区_国产精品久久久久毛片软件_亚洲精品无码aⅴ中文字幕蜜桃_91丨九色丨国产在线观看_精品亚洲国产成人_肉色欧美久久久久久久免费看 | 国产AV第一次处破_少妇日p_淫片在线看_国内精品久久久久影视_欧美日韩福利视频_视频一区视频二区视频三区高_久久曰欧洲_国产亚洲精品美女在线 | 一级大片网站_亚洲国产aⅴ精品_玖玖在线国产_欧美一区二区在线视频_97精品久久中文_久久爱9191_国产精品日韩欧美一区二区_精品资源在线 | 日本高清中文字幕一区二区三区a_少妇精品久久久一区二区三区_人禽l交免费视频_中文在线一区二区_色婷婷久久99综合精品jk白丝_国产人妖网站_国产剧情久久久_欧美日在线观看 | 精品久久乐_亚洲色无色A片一区二区农夫_婷婷色国产精品视频一区_亚洲免费永久精品_日本婷婷_个人极品色综合_日韩三级黄色毛片_一区二区国产高清视频在线 | 国产精品久久久久久中文字_五月天黄色av_国产一级淫秽免费黄色视频_在线免费观看av不卡_天天躁狠狠躁都躁200次_色小妹三区_特级特黄aaaa免费看_亚洲欧美另类成人综合图片 | A级国产乱理论片在线观看_日本少妇被添爽A片动漫_国产一区亚洲_久久永久视频_91精品国产成人_亚洲一区二区三区四区中文字幕_最新欧美一区二区_天天干天天干天天干天天干天天干 | 欧美性猛交性大交_色午夜一av男人的天堂_国产精品永久久久_亚洲夜幕久久日韩精品一区_久热精品视频在线观看_精品超碰_欧美视频一级片_草草草久久久 | 亚洲av日韩av无码尤物_不卡亚洲精品_337P亚洲日本中国大胆69_国产伦精品一区二区三区在线观_日韩精品一区二区三区丰满_fxⅹee性欧美_日本三级日本三级日本三级_亚洲精品乱码久久久久久日本 | 欧美亚洲综合色_四虎影视国产精品永久在线_日韩欧美综合一区_污污网站视频在线观看_日本少妇重口xxxx_久久久久久久久久久韩国男女_中文乱码人妻系列一区_中文字幕精品亚洲 | 无码av动漫精品专区_在线视频免费观看www_中文字幕一区久_97就去干_ww国产_国产在线观看91精品一区_免费欧美日韩_好吊一区二区三区 | 久久与欧美_精品一区亚洲_久久人人精_精品一区日韩成人_91五月色国产在线观看_久久精品视频12_久久人人爽人人爽人人片亞洲_狠狠久久五月精品中文字幕 | 久久99国产精品久久99果冻传媒_亚洲成人精品女人久久久_a一区二区三区_九九综合_青草青草久热精品视_日韩观看_yellow免费观看网站_久久精品高清视频 | 免费国产片在线观看_狠狠操狠狠插_久久好视频_深夜视频在线看_在线免费观看av网_国产毛片精品一区二区_免费在线观看电视网站_欧美在线观看成人 | 777yyy亚洲精品一区二区_亚洲人人舔人人_国产精品乱战久久久_国产免费福利视频一区二区_国产欧美精品一区_久久久国产成人_午夜入口_亚洲热在线免费观看一二三区 | 99久久国产综合麻豆99久久_国产精品一区久久人人爽_国产亚洲精品久久久久久禁果tv_日日躁狠狠躁aaaaxxxx_成年肉动漫在线观看无码_蜜桃视频网站www_国产成人欧美一区二区三区_91欧美精品成人综合在线观看 | 欧美国产伦久久久久久_雨宫琴音av一区在线播放_欧美在线看片a免费观看_九九久久视频_不卡一区_日韩最新在线_特黄做受又粗又长又大又硬_台湾一级毛片永久免费 | 日日摸夜夜骑_又大又黄又粗高潮免费_最好看的中文在线观看_99国产精品无码专区_黄骗免费网站_69网站在线观看_日本在线看片免费大黄_国产精品久久久久久久久久 | 色综合色欲色综合色综合色综合r_成人免费ā片在线观看_噜噜噜在线观看播放视频_FREE性中国熟女HD_久久久经典_国产区久久_日韩精品久久久免费观看夜色_三影院老子影院午夜伦不卡 | 日韩精品免费一区二区在线观看_狠狠操图片_少妇高潮大叫好爽_中国精品久久久_亚洲成人少妇_福利在线国产_日产免费自线一二区_好紧好爽午夜视频 | 欧美色道_国产精品7m视频_久久精品16_亚洲va中文在线播放免费_亚洲熟妇另类久久久久久_毛片毛片毛片毛片毛片毛片毛片毛片毛片毛片_久久精视频_永久免费观看美女裸体视频的网站 | 色天天天综合色天天_亚洲中文字幕一区精品自拍_国产v亚洲v天堂无码_国产av福利第一精品导航_狠狠狠狠狠干_在线资源观看_日本视频在线_巨大黑人极品videos精品 | 91资源在线播放_中文字幕与邻居少妇性刺激_欧美国产大片_国产日韩区_v片在线免费观看_亚洲色欲色欲www网_日本高清一级片_乱人伦人妻中文字幕无码 | 国产精国产精品_婷婷精品国产亚洲AV麻豆不片_国产视频p_九色国产精品_国产特黄色片_无限资源日本_国产精品综合久久久久久_偷拍视频一区二区三区 |